Overview
The easYgen-2300 Series is a compact, affordable genset control and protection package for load sharing up to 16 gensets in island operation, or parallel operation of a single unit with a utility. Its integrated load dependent start/stop programming allows you to define how gensets are brought on- and off-line to support changing load demands. It equally works with a mix of different sized engines, so you can maintain the spinning reserve you need while optimizing fuel efficiency.
The easYgen-2300 Series works with many common industrial interfaces:
- CANopen for peer-to-peer load sharing
- J1939 for engine ECU;
- Modbus RTU for PLC, HMI, and SCADA
- Modem for remote control and programming using Woodward ToolKit software
Highlights
- Island, mains parallel & AMF operation
- Load sharing and loaddependent start/stop for up to 16 units
- Synchronization with phase matching and slip frequency
- Load transfer programs
- Soft loading features
- Open/closed transition
- CANopen / J1939 ECU Control
- Freely configurable discrete & analog I/Os
- Multi-lingual display
- Fast configuration by partial setting files
- Modbus RTU Protocol
- Support of asynchronous generators
- Generator kWh/kvarh meter
- Dynamic mains stabilization (as per BDEW)
- QV monitoring
Features
- Operation modes: Auto, Stop, Manual, and Load/No Load test modes via discrete input possible
- Breaker control: Slip frequency / phase matching synchronization, open-close control, breaker monitoring
- Load transfer features: open / closed transition, interchange, soft loading / soft unloading, mains parallel
- Remote control via interface and discrete/analog inputs for adjusting speed, frequency, voltage, power, reactive power, and power factor set points
- Active power and reactive power load sharing with up to 16 units including load-dependent start/stop
- Operating hours/start/maintenance counters – Operating hours also available from a connected ECU via
J1939/CAN - Supported ECU: Scania EMS/S6, Deutz EMR2, Volvo EMS2, MTU ADEC ECU7/8, Woodward EGS, MAN EDC 7, SISU EEM2/3, Cummins, Perkins and J1939 standard messages
- Multi-lingual capability (11 languages in 1 unit configurable: English, German, French, Spanish, Chinese, Japanese, Italian, Portuguese, Turkish, Russian, Polish)
- Event recorder (300 events, FIFO) with real time clock (battery backed; min. 5 years)
- 128×64 dot graphical interactive LC display with soft keys
- Start/stop logic for Diesel/Gas engines
- Engine pre-glow or purge control
- Warm-up control via timer or coolant temperature
- PC and/or front panel configurable (ToolKit software)
- Multi-level password protection
- Discrete I/O expansion board connectivity (Woodward IKD 1 or Phoenix Contact IL series)Three switchable parameter sets of AC system winding, Rated Voltage, Rated Frequency, Rated Current, Rated Power, Rated Speed
- Can be applied on pumping units as an indicating instrument (relays are inhibited)
- Can be configured from a computer via USB or from the front panel with password protection
- Manual breaker operation with tactile buttons on front panel
- Custom boot-up logo with adjustable screen display time
- Multilingual customizable user interface
Details
Power supply | 12/24 Vdc (8 to 40 Vdc) |
---|---|
Intrinsic consumption | max.~ 8 W (easYgen-2200) |
Maximum supply voltage 120 Vac [1] | 86/150 Vac |
Minimum supply voltage 480 Vac [4] | 346/600 Vac |
Accuracy | Class 1 |
Measuring frequency | 50/60 Hz (40 to 85 Hz) |
Max. power consumption per path | < 0.15 W |
Burden | < 0.15 VA |
Discrete inputs | isolated |
Input range | 12/24 Vdc (8 to 40 Vdc) |
Input resistance | approx. 20 kOhms |
Relay outputs | potential free |
Contact material | AgCdO |
Analog inputs (none isolated) | freely scalable |
Analog outputs (isolated) | freely scalable |
Insulation voltage (continuously) | 100 Vac |
Resolution | 11/12 Bit (depending on output) |
Housing (Front panel flush mounting) | Plastic housing |
Dimensions (WxHxD) | 219 × 171 × 61 mm |
Front cutout (WxH) | 186 [+1.1] × 138 [+1.0] mm |
Connection | screw/plug terminals 2.5 mm² |
Front | insulating surface |
Weight | approx. 800 g |
Listings | UL, cUL, GOST-R |
Marine | LR (Type Approval), ABS (Design Assessment) |
Disturbance test (CE) | tested according to applicable EN guidelines |
Reviews
There are no reviews yet.